Determine Module Slot Location
The figure below shows chassis slot numbering in a 4-slot chassis. Slot 0 is the 
first slot and is always the leftmost slot in the rack (the first slot to the right of 
the power supply). You can use any size ControlLogix chassis and install the 
module in any slot. You can also install multiple 1756-DHRIO modules in the 
same chassis. You can install as many modules as your power supply can 
accommodate, that is, number for which the power supply is rated.
Install or Remove the Module While Power Is Applied
You can install or remove the module while chassis power is applied if you 
observe the following precautions.
Be sure that power is removed or the area is nonhazardous before proceeding. 
Repeated electrical arcing causes excessive wear to contacts on both the 
module and its mating connector. Worn contacts may create electrical 
resistance that can affect module operation.
WARNING
When you insert or remove the module while backplane power is on, an 
electrical arc can occur. This could cause an explosion in hazardous location 
installations.
Chassis
Power 
Supply
Slot 0
Slot 1
Slot 3
Slot 2