I/O Interface and System Design

Chapter 2

2-3

When selecting devices to use with the block I/O inputs, verify that the
on–state voltage and currents of the device fall into the on–state region for
the block input. Also verify that the off–state current and voltage fall into
the off–state region of the block I/O module (Figure 2.1).

Figure 2.1

dc Input Specifications

ЙЙЙЙЙЙ

ЙЙЙЙЙЙ

ЙЙЙЙЙЙ

ЙЙЙЙЙЙ

ЗЗЗЗЗЗЗЗЗЗЗЗЗЗЗ

ЗЗЗЗЗЗЗЗЗЗЗЗЗЗЗ

ЗЗЗЗЗЗЗЗЗЗЗЗЗЗЗ

ЗЗЗЗЗЗЗЗЗЗЗЗЗЗЗ

ЗЗЗЗЗЗЗЗЗЗЗЗЗЗЗ

11mA

Minimum offĆstate = 1.5mA

0

5.0

30

Voltage

Current

On

Off

0

Off

Minimum onĆstate = 2.5mA

10

On

Undefined or

Transition Region

Figure 2.2

ac Input Specifications at 60Hz

12.3mA

Minimum offĆstate = 2.3mA

0

35

132

Voltage

Current

0

79

Off

ЙЙЙЙЙЙ

ЙЙЙЙЙЙ

ЙЙЙЙЙЙ

ЙЙЙЙЙЙ

ЗЗЗЗЗЗЗЗЗЗЗЗЗЗЗ

ЗЗЗЗЗЗЗЗЗЗЗЗЗЗЗ

ЗЗЗЗЗЗЗЗЗЗЗЗЗЗЗ

ЗЗЗЗЗЗЗЗЗЗЗЗЗЗЗ

ЗЗЗЗЗЗЗЗЗЗЗЗЗЗЗ

On

Off

Undefined or

Transition Region

Minimum onĆstate = 5.0mA