I/O Interface and System Design
Chapter 2
2-3
When selecting devices to use with the block I/O inputs, verify that the
on–state voltage and currents of the device fall into the on–state region for
the block input. Also verify that the off–state current and voltage fall into
the off–state region of the block I/O module (Figure 2.1).
Figure 2.1
dc Input Specifications
ЙЙЙЙЙЙ
ЙЙЙЙЙЙ
ЙЙЙЙЙЙ
ЙЙЙЙЙЙ
ЗЗЗЗЗЗЗЗЗЗЗЗЗЗЗ
ЗЗЗЗЗЗЗЗЗЗЗЗЗЗЗ
ЗЗЗЗЗЗЗЗЗЗЗЗЗЗЗ
ЗЗЗЗЗЗЗЗЗЗЗЗЗЗЗ
ЗЗЗЗЗЗЗЗЗЗЗЗЗЗЗ
11mA
Minimum offĆstate = 1.5mA
0
5.0
30
Voltage
Current
On
Off
0
Off
Minimum onĆstate = 2.5mA
10
On
Undefined or
Transition Region
Figure 2.2
ac Input Specifications at 60Hz
12.3mA
Minimum offĆstate = 2.3mA
0
35
132
Voltage
Current
0
79
Off
ЙЙЙЙЙЙ
ЙЙЙЙЙЙ
ЙЙЙЙЙЙ
ЙЙЙЙЙЙ
ЗЗЗЗЗЗЗЗЗЗЗЗЗЗЗ
ЗЗЗЗЗЗЗЗЗЗЗЗЗЗЗ
ЗЗЗЗЗЗЗЗЗЗЗЗЗЗЗ
ЗЗЗЗЗЗЗЗЗЗЗЗЗЗЗ
ЗЗЗЗЗЗЗЗЗЗЗЗЗЗЗ
On
Off
Undefined or
Transition Region
Minimum onĆstate = 5.0mA