Configuring Your Block I/O for PLC

Family Programmable Controllers

Chapter 4

4-5

The SLC 500 controllers communicate with the block I/O using an I/O
Scanner module (cat. no. 1747-SN series A). Refer to the user manual for
the 1747-SN/A Scanner module for more information.

Note: These block I/O modules are not compatible with the 1747-DSN
Distributed I/O Scanner module.

Each block I/O module uses 2 words of output image table memory and 2
words of input image table memory. Each block occupies 1/4 rack of data
table, with 4 blocks comprising 1 logical rack. Image table usage for one
assigned rack number and examples of image table usage are shown in
Figures 4.2 through 4.10.