I/O Interface and System Design

Chapter 2

2-8

Relay Output

The relay outputs on block I/O modules are electro-mechanical outputs and
do not require specific compatibility with the load device as to current
sinking or sourcing.

Figure 2.10

Simplified Schematic of Relay Output Circuit

Indication

LED

(logic)

System

Circuitry

12477-I

L1

L2

20-132V ac

R

L

Output

Common

Input/Output

+5V

100

0.033

µ

F

1k

The 16- and 32-point ac and dc block I/O modules are internally fused to
protect the module. No external power fusing is required. Outputs are not
fused. Fusing of outputs is recommended. If desired to fuse an output, you
must provide external fusing.

Table 2.B

Recommended Fuses

Type of

Circuit

Part Number

1

Size

Rating in

Amps

Maximum Surge Current

2

(repeatable every 2s)

ac

SANĆO SS2Ć1.0

0.25 in. x 1.25 in.

1.0A

3.0A for 50ms

ac

SANĆO MQ2Ć1.0

5mm x 20mm

1.0A

2.5A for 50ms

dc

Littelfuse 322 1.25 0.25 in. x 1.25 in.

1.25A

2.25A for 50ms

dc

SANĆO MQ4Ć800

5mm x 20mm

800mA

3

2.0A for 50ms

1

Note: Do not substitute another fuse for those listed.

2

The recommended fuses will withstand surges of the above listed currents for the time specified.

3

Current must be limited to 650mA when using this fuse.

.

Both ac and dc block I/O modules (except relay output modules) are
derated linearly above 30

o

C up to and including 60

o

C, as shown in

Table 2.C.

For modules with relay outputs, refer to Appendix A for output current and
surge current ratings.

Fusing