Installing Block I/O

Chapter 3

3-22

Figure 3.16

Input/Output Wiring Connections for the 1791Ć8BC

Series B

RIO

1

30

PLC and SLC

24V dc

+

Ć

24V dc

+

Ć

24V dc

+

Ć

GND

BLU
CLR

in 00
in 01
in 02
in 03
in 04
in 05
in 06

in 07

RET

in

NOT

USED

SHD

Vdc

out

out 00

out 02
out 03
out 04
out 05
out 06

out 07

Vdc

out

NOT

USED

RET

out

out 01

+24

RET

+24

RET

in

NOT

USED

RET in connections are internally connected together.

Vdc out connections must be externally connected together to accommodate amperage rating.

Output fusing is recommended. Refer to Table 2.B on page 2Ć8.

NOTE:

1

2

29

30

Connections

1791Ć8BC

Series B

Connections

Designation

Description

Terminal No.

Power

+24

+24V dc Power

1

Power

Connections

RET +24

dc Return

3

GND

Chassis ground

2

1

Remote I/O

BLU

Blue wire Ć RIO

6

Remote I/O

Connections

CLR

Clear wire Ć RIO

8

SHD

Shield Ć RIO

7

I/O Connections

Input

in 00 thru in 07

Input 00 thru 07

16, 18, 20, 22, 24, 26, 28, 30

Input

RET in

dc input Return

12, 14

2

Vdc out

dc output Supply

11, 13

3

Output RET out

dc output Return

9

p

out 00 thru out 07

Output 00 thru 07

15, 17, 19, 21, 23, 25, 27, 29

Not used

For internal test only; not

for customer use.

4, 5, 10

1

Connect chassis ground to equipment grounding stud. These are not internally connected.

2

Terminals 12 and 14 are internally connected.

3

Terminals 11 and 13 must be externally connected by customer to accommodate amperage rating.