Installing Block I/O

Chapter 3

3-21

Figure 3.15

Output Wiring Connections for the 1791Ć0B16

Series B

RIO

1

30

PLC

24V dc

24V dc

24V dc

+

Ć

+

Ć

+

Ć

GND

NOT

USED

NOT

USED

BLU

SHD

CLR

RET

2

Vdc

2

out 00

RET

1

Vdc

1

out 01
out 02
out 03
out 04
out 05
out 06

out 07

Vdc

2

out 10

out 12
out 13
out 14
out 15
out 16

out 11

Vdc

1

out 17

+24

RET

+24

RIO

1

30

SLC

24V dc

24V dc

24V dc

+

Ć

+

Ć

+

Ć

GND

NOT

USED

NOT

USED

BLU

SHD

CLR

RET

2

Vdc

2

out 00

RET

1

Vdc

1

out 01
out 02
out 03
out 04
out 05
out 06

out 07

Vdc

2

out 08

out 10
out 11
out 12
out 13
out 14

out 09

Vdc

1

out 15

+24

RET

+24

Note: Vdc 1 connections must be externally connected together to accommodate amperage rating.

Vdc 2 connections must be externally connected together to accommodate amperage rating.

Output fusing is recommended. Refer to Table 2.B on page 2Ć8.

1

2

1

2

29

30

29

30

Connections

1791Ć0B16

Series B

Connections

Designation

Description

Terminal No.

Power

+24

+24V dc Power

1

Power

Connections

RET +24

dc Return

3

GND

Chassis ground

2

1

Remote I/O

BLU

Blue wire Ć RIO

6

Remote I/O

Connections

CLR

Clear wire Ć RIO

8

SHD

Shield Ć RIO

7

I/O Connections

out 00 thru out 07

Output 00 thru 07

16, 18, 20, 22, 24, 26, 28, 30

Output Vdc 1

+24V dc output supply

12, 14

2

p

RET 1

dc output return

10

Vdc 2

+24V dc output supply

11, 13

3

Output

RET 2

dc output return

9

Output

PLC: out 10 thru out 17

SLC: out 08 thru out 15

PLC: Output 10 thru 17

SLC: Output 08 thru 15

15, 17, 19, 21, 23, 25, 27, 29

Not used

For internal test only; not

for customer use.

4, 5

1 Connect chassis ground to equipment grounding stud. These are not internally connected.

2

Terminals 12 and 14 must be externally connected by customer to accommodate amperage rating.

3

Terminals 11 and 13 must be externally connected by customer to accommodate amperage rating.