Installing Block I/O

Chapter 3

3-23

Figure 3.17

Input/Output Wiring Connections for the 1791Ć8BR

Series B

RIO

1

30

PLC and SLC

24V dc

+

-

24V dc

+

-

GND

BLU
CLR

in 00

in 01

in 02

in 03

in 04

in 05

in 06

in 07

RET

in

NOT

USED

SHD

out 00

out 02

out 03

out 04

out 05

out 06

out 07

Vac/dc

out

NOT

USED

out 01

+24

RET

+24

RET

in

NOT

USED

12399-I

NOT

USED

RET in connections are internally connected together.

Vac/dc out connections must be externally connected together to accommodate amperage rating.

Output fusing is recommended. Refer to Table 2.B on page 2Ć8.

NOTE:

29

30

1

2

ac/dc

L1/+ L2N/-

Vac/dc

out

Connections

1791-8BR Series B

Connections

Designation

Description

Terminal No.

Power

+24

+24V dc Power

1

Power

Connections

RET +24

dc Return

3

GND

Chassis ground

2

1

Remote I/O

BLU

Blue wire - RIO

6

Remote I/O

Connections

CLR

Clear wire - RIO

8

SHD

Shield - RIO

7

I/O Connections

Input

in 00 thru in 07

Input 00 thru 07

16, 18, 20, 22, 24,

26, 28, 30

Input

RET in

dc input Return

12, 14

2

Vac/dc out

ac or dc Output Supply

11, 13

3

Output

out 00 thru out 07

Output 00 thru 07

15, 17, 19, 21, 23,

25, 27, 29

Not used

For internal test only; not

for customer use.

4, 5, 9, 10

1

Connect chassis ground to equipment grounding stud. These are not internally connected.

2

Terminals 12 and 14 are internally connected.

3

Terminals 11 and 13 must be externally connected by customer to accommodate amperage rating.