Selecting remote i/o link speed, 3ć38 – Rockwell Automation 1791-XXXX Discrete I/O AC and DC Block I/O Input and Output Modules User Manual

Page 57

Advertising
background image

Installing Block I/O

Chapter 3

3-38

Certain products are not compatible with extended node capabilities
obtained with the use of 82 ohm terminators. Table 3.D lists those products
that are not compatible.

Table 3.D

NonĆcompatible Products

Device

Series

Scanners Ć

1771ĆSN

All

1772ĆSD

All

1772ĆSD2

All

1775ĆSR

All

1775ĆS4A

All

1775ĆS4B

All

Adapters Ć

1771ĆAS

All

1771ĆASB

Series A

1771ĆDCM

All

Miscellaneous Ć

1771ĆAF

All

1771ĆAF1

All

The remote I/O link can operate at three speeds: 57.6K, 115.2K or 230.4K
bits/s. The selection of link speed is dependent on the scanner/processor
used, throughput requirements, distance required and the type of remote
I/O devices being used.

Throughput Requirements

The throughput, a portion of which is I/O scan time, must be balanced
against the distance requirements for the application. The typical discrete
I/O scan time is shown in Table 3.E below. Use these values along with
your processor/scanner manual to determine system throughput.

Table 3.E

I/O Scan Time vs. Remote I/O Link Distance

57.6K Bits/s

115.2K Bits/s

230.4K Bits/s

Typical Discrete I/O Scan

Time (each block)

10ms

7.0ms

3ms

Remote I/O link distance

10,000 ft.

5,000 ft.

2,500 ft.

Compatibility of 1771 I/O

Products with Extended

Node Numbers

Selecting Remote I/O Link

Speed