Installing block i/o chapter 3, Series b – Rockwell Automation 1791-XXXX Discrete I/O AC and DC Block I/O Input and Output Modules User Manual

Page 26

Advertising
background image

Installing Block I/O

Chapter 3

3-7

Figure 3.6

Output Wiring Connections for the 1791Ć0A16

Series B

RIO

L2/N

L1

L2/N L1

1

30

SLC

L2/N

L1

L1

GND

N

NOT

USED NOT

USED

BLU

SHD

out 00
out 01
out 02

out 03
out 04
out 05
out 06

out 07

out 08

out 10
out 11
out 12
out 13
out 14

out 09

out 15

CLR

COM

1

COM

2

COM

2

NOT

USED

COM

2

L1

GND

BLU

SHD

out 02

out 03
out 04

out 05

out 06

out 08

out 10
out 11
out 12
out 13
out 14

out 09

out 15

COM

1

COM

1

out 00
out 01

CLR

NOT

USED

N

out 07

RIO

L2/N

L1

L2/N L1

1

30

PLC

L2/N

L1

L1

GND

N

NOT

USED NOT

USED

BLU

SHD

out 00
out 01
out 02
out 03
out 04
out 05
out 06

out 07

out 10

out 12
out 13
out 14
out 15
out 16

out 11

out 17

CLR

L1Ć1 connections must be externally connected together to accommodate total amperage.

L1Ć2 connections must be externally connected together to accommodate total amperage.

Output fusing is recommended. Refer to Table 2.B on page 2Ć8.

NOTE:

L1-1

L1-1

L1-1

L1-2

L1-2

L1-2

L1-1

L1-1

L1-1

L1-2

L1-2

L1-2

1

2

1

2

29

30

29

30

Connections

1791Ć0A16

Series B

Connections

Designation

Description

Terminal

Power

L1

ac hot

1

Power

Connections

N

ac neutral

3

GND

Chassis ground

2

1

Remote I/O

BLU

Blue wire Ć RIO

6

Remote I/O

Connections

CLR

Clear wire Ć RIO

8

SHD

Shield Ć RIO

7

I/O Connections

Output

out 00 thru out 07

Output 00 thru 07

16, 18, 20, 22, 24,

26, 28, 30

Output

L1-1

L1 output supply

10, 12, 14

2

L1-2

L1 output supply

9, 11, 13

3

Output

PLC: out 10 thru out 17

SLC: out 08 thru out 15

PLC: Output 10 thru 17

SLC: Output 08 thru 15

15, 17, 19, 21, 23,

25, 27, 29

Not used

For internal test only; not for

customer use.

4, 5

1 Connect chassis ground to equipment grounding stud. These are not internally connected.

2 Terminals 10, 12 and 14 must be externally connected by customer.

3 Terminals 9, 11 and 13 must be externally connected by customer.