Installing Block I/O

Chapter 3

3-15

Connections

1791-16AC Series B

Connector/Terminal

Connections

Designation

Description

Left Conn. Right Conn.

Power

L1

ac hot

1

Power

Connections

N

ac neutral

3

GND

Chassis ground

2

1

Remote I/O

BLU

Blue wire - RIO

6

Remote I/O

Connections

CLR

Clear wire - RIO

8

SHD

Shield - RIO

7

I/O Connections

in 00 thru in 07

Input 00 thru 07

16, 18, 20,

22, 24, 26,

28, 30

Input

COM 1

L2/N Input Common

10, 12, 14

2

Input

(G)

6

COM 2

L2/N Input Common

9, 11, 13

3

PLC: in 10 thru in 17

SLC: in 08 thru in 15

PLC: Input 10 thru 17

SLC: Input 08 thru 15

15, 17, 19,

21, 23, 25,

27, 29

PLC: out 00 thru 07

SLC: out 00 thru 07

PLC: Output 00 thru 07

SLC: Output 00 thru 07

15, 13, 11,

9, 7, 5, 3, 1

Output

L1-3

L1 output supply

21, 19, 17

4

Output

(G

)7

PLC: out 10 thru 17

SLC: out 08 thru 15

PLC: Output 10 thru 17

SLC: Output 08 thru 15

16, 14, 12,

10, 8, 6, 4, 2

L1-4

L1 output supply

22, 20, 18

5

Not used

For internal test only;

not for customer use.

4, 5

29, 27, 26

No Conn

No internal connection;

customer can use.

30, 28, 25,

24, 23

1 Connect chassis ground to equipment grounding stud. These are not internally connected.

2 Terminals 10, 12 and 14 are internally connected together.

3 Terminals 9, 11 and 13 are internally connected together.

4 Terminals 17, 19 and 21 must be externally connected by customer to accommodate total amperage.

5 Terminals 18, 20 and 22 must be externally connected by customer to accommodate total amperage.

6

IN (G) = input module group.

7

OUT (G) = output module group.