Start the programming software, Power up the system – Rockwell Automation 1785-Lx0C15 ControlNet PLC-5 Programmable Controllers Quick Start User Manual
Page 22
 
Publication 1785-QS006C-EN-P - April 2002
3-2
Set Up the Software
Start the Programming 
Software
Start the programming software by following the procedures 
described in your programming software documentation.
If you have difficulty, verify that the power supply is turned on.
Power Up the System
Power up the system if you have not done so already. Check the LED 
display on the processor. If your system is operating properly, the 
PROC LED should be steady red and the message 
“Processor RAM
is faulted. Press <Enter> to clear memory”
should appear on
the programming software display. See the following table to 
proceed. If the PROC LED is not red, turn to chapter 4 for 
troubleshooting information.
To monitor your system as you configure and run it, check the 
processor LED display for the following indicators:
If your keyswitch 
is in this position:
do this:
PROGRAM
Clear memory. The PROC LED should turn off.
The software is in Program mode.
REMOTE
Clear memory. The PROC LED should turn off.
The software is in Remote Program mode.
RUN
You see the message “
No access or
privilege violation
” because you cannot
clear memory in Run mode. Change the keyswitch
position to Program or Remote and press <Enter> to
clear memory.
This LED:
lights when:
COMM
you establish serial communication (CH 0)
BATT
no battery is installed or the battery voltage is low
REM I/O
you establish Remote I/O communication
ADAPT
the processor is in adapter mode
FORCE
forces are present in your ladder program