Publication 1785-QS006C-EN-P - April 2002

4-6

Troubleshoot the Processor System

Monitor ControlNet Configuration
and Status

Use the following software packages to montior ControlNet
configuration and status information.

For information about using these software packages, see the online
help systems for RSNetWorx for ControlNet and RSLogix5 software.

Use:

To:

RSNetWorx for ControlNet

define ControlNet network parameters, such as:
• network update time
• media redundancy
• physical media configuration
• maximum scheduled nodes
• maximum unscheduled nodes
• monitor I/O map entry status

RSLogix5

• monitor ControlNet diagnostic file

1

• enter user program files
• create/delete/monitor data table files
• enter module configuration
• enter channel 0, 1A, 1B, and, 3 configuration
• administer passwords and privileges

RSLinx

to provide the ControlNet network interfaces to:
• poll the network for active devices
• monitor station diagnostics

1

It is highly recommended that you declare an extended ControlNet diagnostic file (63

words) using RSNetWorx. This file will allow you to monitor for noise (via ladder and HMI

query), to monitor the overall health of scheduled connections (words 40 and 41), and to

monitor ControlNet buffer usage.