Rockwell Automation 1785-Lx0C15 ControlNet PLC-5 Programmable Controllers Quick Start User Manual

Page 31

Advertising
background image

Publication 1785-QS006C - April 2002

A-3

PLC-5/20C15 PLC-5/40C15 PLC-5/46C15 PLC-5/80C15

Maximum User Memory Words

16K

48K

1

48K

1

100K

2

Maximum Total

I/O

Any Mix

512

2048

2048

3072

Complimentary

512 in and 512

out

2048 in and

2048 out

2048 in and

2048 out

3072 in and

3072 out

Program Scan Time

0.5 ms per K word (bit logic)

2 ms per K word (typical)

ControlNet I/O

3

Transmission Rate

5M bit/s

Network Update Time (NUT)

2-100 ms (user selectable)

Number of ControlNet Ports

1 (redundant)

Maximum Number of Nodes per Link without a Repeater

48—with 250 m (approx. 820 ft) cable length

Maximum Number of Nodes per Link with Repeaters

99

Maximum Link Cable Length without a Repeater

1,000 m (approximately 3,280 ft)—with 2 nodes

500 m (approximately 1,640 ft)—with 32 nodes

250 m (approximately 820 ft)—with 48 nodes

Maximum Number of I/O Map Entries

64

96

96

128

Maximum DIF/DOF Size

2000 words

3000 words

3000 words

4000 words

Maximum Link Cable Length with Repeaters

6,000 m (approximately 19,680 ft)—with 2 nodes

3,000 m (approximately 9,840 ft)—typical

Remote I/O and

DH+

Transmission Rate

57.6K bit/s

115.2K bit/s
230.4K bit/s

I/O Scan Time (Typical)

10 ms per rack @ 57.6K bit/s
7 ms per rack @ 115.2K bit/s

3 ms per rack @ 230K bit/s

Maximum Number of Remote I/O Racks

3

15

15

23

Maximum Number of Remote I/O Devices

12

60

60

92

Number of Ports Configurable for DH+ or Remote I/O

(Adapter or Scanner)

1

2

2

2

Number of Dedicated DH+ Ports

1

0

0

0

Number of Serial Ports

1

Number of Coprocessor Ports

1

Maximum Number of MCPs

16

1

The PLC-5/40C15 and -5/46C15 processors have a limit of 32K words per data-table file.

2

The PLC-5/80C15 processor has a limit of 56K words per program file and 32 K words per data table file. The PLC-5/80C processor has 64K words of total data

table space.

3

For more information, see the ControlNet Cable System Planning and Installation Manual, publication 1786-6.2.1.

Advertising