Troubleshoot the Processor System

Indicator

Color

1

Probable Cause

Recommended Action

Off

Internal diagnostics failed

1. Turn power off, make sure ControlNet address is

not 00, reseat processor, then power up
2. Clear memory and reload your program
3. Replace EEPROM with new program
4. If still an error, replace the processor

No power

Check power supply

Steady Red

Faulted unit

Cycle power or reset unit

If fault persists, contact your Allen-Bradley Company,

Inc. representative or distributor

Flashing

Green

Normal operation if processor is in

FLASH memory program mode

No action required

Flashing

Red/Green

The processor’s ControlNet address

is above UMAX

Configure the ControlNet network so that UMAX is at

least as high as the processor’s ControlNet address.

Set the processor’s ControlNet address at or below

UMAX.

Alternating

Red/Green

Self-test

No action required

Alternating

Red/Off

Incorrect node configuration

Check network address and other ControlNet

configuration parameters

Off

Channel disabled

No action required

Configure for ControlNet communication

Steady

Green

Normal operation

No action required

Flashing

Green/Off

Temporary errors

No action required

Make sure that ControlNet is properly terminated

Flashing

Red/Off

Media fault

Check media for broken cables, loose connectors,

missing terminators, etc.

No other nodes present on network

Add other nodes to the network

Flashing

Red/Green

Incorrect network configuration

Cycle power or reset unit

If fault persists, contact your Allen-Bradley Company,

Inc. representative or distributor

1

Definition of terms:

alternating – the two indicators alternate between the two defined states at the same time (applies to both indicators viewed

together); the two indicators are always in opposite states, out of phase

flashing – the indicator alternates between the two defined states (applies to each indicator viewed independent of the other); if both

indicators are flashing; they flash together, in phase

steady – indicator is on continuously in the defined state