General

This table lists general specifications.

Backplane Current

1785-L20C15:

2.7A @ 5Vdc

1785-L40C15, -L46C15, -L80C15: 3.3A @ 5Vdc

Heat Dissipation

1785-L20C15: 54

BTU/hour

1785-L40C15, -L46C15, -L80C15: 59 BTU/hour

Adjacent Slot Power

Dissipation

10W maximum

Operating Temperature

IEC 60068-2-1 (Test Ad, Operating Cold),

IEC 60068-2-2 (Test Bd, Operating Dry Heat),

IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
0-60

o

C (32–140

o

F)

Storage Temperature

IEC 60068-2-1 (Test Ab, Un-packaged Non-operating Cold),

IEC 60068-2-2 (Test Bc, Un-packaged Non-operating Dry Heat),

IEC 60068-2-14 (Test Na, Un-packaged Non-operating Thermal Shock):
–40 to 85

o

C (–40 to 185

o

F)

Relative Humidity

IEC 60068-2-30 (Test Db, Un-packaged Non-operating

Damp Heat):

5–95% non condensing

Vibration

IEC60068-2-6 (Test Fc, Operating):

2g @10–500Hz

Shock

IEC60068-2-27:1987, Test Ea (Unpackaged shock, ES#002)

Operating - 30g

Non-operating - 50g

Emissions

CISPR 11:

Group 1, Class A (with appropriate enclosure)

ESD Immunity

IEC 61000-4-2:

4kV contact discharges

Radiated RF Immunity

IEC 61000-4-3:

10V/m, 3V/m Broadcast Bands, with 1kHz sine-wave 80% AM from 30MHz to 1000Mhz

EFT/B Immunity

IEC 61000-4-4:

+2kV at 5kHz on communications ports

Surge Transient Immunity

IEC 61000-4-5:

+2kV line-earth(CM) on signal ports

Conducted RF Immunity

IEC 61000-4-6:

10Vrms with 1kHz sine-wave 80%AM from 150kHz

to 30MHz

Enclosure Type Rating

None (open style)

Time-of-Day
Clock/Calendar

1

Maximum Variations at 60

°

C:

±

5 min per month

Typical Variations at 20

°

C:

±

20 s per month

Timing Accuracy:

1 program scan

Available Cartridges

1785-CHBM ControlNet Hot Backup Cartridge

2

(required for each processor used in a hot backup system)
1785-RC Relay Cartridge

Battery

Allen-Bradley 1770-XYC

1

The clock/calendar will update appropriately each year.

2

The 1785-CHBM cannot be used with the 1785-5/60C processor.

3

The 1785-ME16 cannot be used with ControlNet PLC-5 processors.

4

For more information, refer to publication 1770-4.1,