background image

Publication 1785-QS006C-EN-P - April 2002

Troubleshoot the Processor System

4-5

Use the DH+/RIO
Status Indicators

Indicator

Color

Channel Mode

Description

Probable Cause

Recommended Action

A or B

Green

(steady)

Remote I/O

Scanner

Active Remote I/O link, all

adapter modules are

present and not faulted

Normal

operation

No action required

Remote I/O

Adapter

Communicating with

scanner

DH+

Processor is transmitting

or receiving on DH+ link

Green

(blinking

rapidly or

slowly)

Remote I/O

Scanner

At least one adapter is

faulted or has failed

• Power off at

remote rack

• Cable broken

• Restore power to the

rack

• Repair cable

DH+

No other nodes on network

Red

(steady)

Remote I/O

Scanner
Remote I/O

Adapter
DH+

Hardware fault

Hardware error

• Turn power off, then

on.

• Check that the

software

configurations

match the hardware

set-up.

• Replace the

processor.

Red

(blinking

rapidly or

slowly)

Remote I/O

Scanner

Faulted adapters detected

• Cable not

connected or

is broken

• Power off at

remote racks

• Repair cable

• Restore power to

racks

DH+

Bad communication on

DH+

Duplicate node

detected

Correct station address

Off

Remote I/O

Scanner
Remote I/O

Adapter
DH+

Channel offline

Channel is not

being used

Place channel online if

needed

Advertising