3-14 Installing and Configuring Your ControlNet PLC-5 Backup System

6. Right click on the odd-numbered node (Node 1 in this example)

and choose Insert Connection.

The Connection dialog box appears. The To Node field is
already filled in for you. This number indicates the node number
from which you will receive the Consume Buffer ID message. In
your ControlNet backup system, the odd-numbered node will
receive the message from the even node, and vice versa.

7. Repeat steps 2 through 4, creating a Consume Buffer ID message

for the even-numbered node.

8. Record the Produce Buffer ID and Consumer Buffer ID message

numbers from the odd-numbered PLC-5 below:

Produce Buffer ID message number:__________

Consume Buffer ID message number:__________

You will use these numbers later in the configuration process.

Reconfigure ControlNet I/O on the Second PLC-5

Reconfigure all ControlNet I/O adapters and modules that will be in
your ControlNet PLC-5 backup system by changing their ControlNet
connection from Exclusive Owner (default) to Redundant Owner.

1. Launch RSNetWorx for ControlNet.

2. Check the Edits Enabled checkbox on the toolbar.

3. Right click on the second PLC-5 processor (the even-numbered

node) and choose Scanlist Configuration.