Publication 1785-UM024B-EN-P - January 2003

Installing and Configuring Your ControlNet PLC-5 Backup System 3-17

9. Set the following:

Backup File - Enter an unused data file number. This creates

a 200-word integer file to be used as the ControlNet Backup
Configuration and Status file.

Odd Node Address - Enter the ControlNet node address

corresponding to the odd node processor.

Send Message - Enter the message number of the from the

Produce Buffer ID from the odd-numbered node address
(refer to the number you recorded on page 3-6.)

Receive Message - Enter the message number of the

Consume Buffer ID from the odd-numbered node address
(refer to the number you recorded on page 3-6.)

If your system is properly configured, the PRI and SEC LEDs on
the first processor’s backup cartridge are off.

10. Save the configuration.

11. Repeat steps 1 through 10 for the second processor, saving the

configuration under a different name.

The QUAL LED on both processors should now be yellow, and
you have a fully qualified backup system. If desired, you can
now go to Run mode.