Installing and Configuring Your ControlNet PLC-5 Backup System 3-15
The Scanlist Configuration screen appears.
4. For each I/O adapter entry under the Connection Name
column, double click on Exclusive Owner, choose Redundant
Owner from the pull-down menu, and press Enter.
5. From the File menu, choose Save to save the completed
ControlNet configuration.
Configure the Hot Backup Parameters on the First PLC-5
1. Launch RSLogix 5.
2. Go online with the odd-numbered ControlNet node.
3. From the Comms menu, choose System Comms.
The Communications dialog appears:.
4. Click on the odd-numbered node address of the first PLC-5.