Publication 1785-UM024B-EN-P - January 2003

Installing and Configuring Your ControlNet PLC-5 Backup System 3-25

For the point-to-point DH+ network between the processors, set the
DH+ address based upon the ControlNet node address being an even
or odd number, as shown in the following table:

Reasons for invalid crossload channel configuration:

• Channel 1A must be configured as DH+
• Channel 1A baud rate must be 230.4Kbaud
• Odd-numbered ControlNet PLC-5 DH+ address must be 1
• Even-numbered ControlNet PLC-5 DH+ address must be 2

Correct this by changing the DIP switch to their proper positions
as shown in the above table.

Make the setting in RSLogix 5:

1. In the ControlNet Hot Backup Screen, choose the Crossload tab.

2. In the Crossload Channel dialog, toggle from Channel 2 to

Channel 1A.

If the PLC-5 is not in the invalid backup state, the feature is properly
configured.

To set:

Set
switch(es):

To:

an odd-numbered ControlNet address 1

Up

2-6

Down

an even-numbered ControlNet address 1

Down

2

Up

3-6

Down

Baud Rate

7

Up
(230.4kbps)