Using the 1785-chbm cartridge status indicators, Using the 1785-chbm cartridge status indicators -3 – Rockwell Automation 1785-CHBM ControlNet PLC-5 Hot Backup System User Manual User Manual

Page 67

Advertising
background image

Publication 1785-UM024B-EN-P - January 2003

Monitoring and Troubleshooting Your ControlNet PLC-5 Hot Backup System 5-3

Using the 1785-CHBM
Cartridge Status Indicators

The 1785-CHBM cartridge status indicators indicate the operational
state of the ControlNet PLC-5 backup system. The following table lists
the various LED states and the recommended action:

LED

Color

Indicates

Probable Cause

Corrective Action

PRI

Green

This processor is the primary (i.e., it controls the
outputs).

Normal operation

No action required

Green blinking

This processor is in the Lonely Primary backup
state

No good scheduled
connections

Check media for broken cables,
loose connectors, missing
terminators, etc.

Red

The backup system is not yet completely
configured (i.e., system is in the Invalid backup
state).

Improper backup
configuration
parameters
Improper ControlNet
Backup Integer file

Refer to Troubleshooting the
Invalid Backup State section,
later in this chapter.

Off

This processor is not the primary (i.e., system is
in the No Control or Secondary backup state).

Normal operation

No action required

SEC

Yellow

This processor is the qualified secondary (i.e.,
system is in the Secondary backup state).

Normal operation

No action required

Red

The backup system is not yet completely
configured (i.e., system is in the Invalid backup
state).

Improper backup
configuration
parameters
Improper ControlNet
Backup Integer file

Refer to Troubleshooting the
Invalid Backup State section,
later in this chapter.

Off

This processor is not the secondary (i.e., system
is in the No Control or Primary backup state).

Normal operation

No action required

QUAL

Green

The system has both a primary and a secondary
processor, which are communicating properly
with each other; the secondary processor is
qualified.

Normal operation

No action required

Yellow

The system has both a primary and a secondary
processor, which are communicating properly
with each other, but the secondary is not yet
qualified.

Normal operation

No action required

Alternating yellow
and green

Qualification active

Normal operation

No action required

Off

The primary and secondary processors are not
communicating properly with each other.

Standalone processor
One or both processors
are in the Invalid
backup state
Improper backup
configuration
parameters

Verify that the connection
parameters (words 0 - 2) of the
ControlNet Backup Integer file
are the same for both processors.