Monitoring and Troubleshooting Your ControlNet PLC-5 Hot Backup System 5-5

If you see reason
code:

Which indicates this condition:

Take this corrective action:

0

Valid backup state

No action required

1

Receive handshake connection not found in I/O Map
Table

Configure the handshake connections in the I/O map table.
Enter the handshake connection numbers in words 1 and 2
of the ControlNet Backup Configuration and Status file.

2

Send handshake connection not found in I/O map
table

Configure the handshake connections in the I/O map table.
Enter the handshake connection numbers in words 1 and 2
of the ControlNet Backup Configuration and Status file.

3

Receive handshake connection wrong size

Make the handshake connection in the I/O map table 5
words long.

4

Send handshake connection wrong size

Make the handshake connection in the I/O map table 5
words long.

5

Node address number wrong

Enter the odd node number of the odd-even backup pair
into word 0 of the ControlNet Backup Configuration and
Status file.

6

Operation mode word invalid

Enter a valid operation mode value into word 10 of the
ControlNet Backup Configuration and Status file.
0 = asynchronous
1 = synchronous

7

Equivalence mode word invalid

Enter a valid equivalence mode word (i.e., 0 - 63) into word
11 of the ControlNet Backup Configuration and Status file.

8

Designated Primary word invalid

Enter a valid Designated Primary word into word 12 of the
ControlNet Backup Configuration and Status file.
0 = inactive
1 = active

9

Maximum Program Scan Time word invalid

Enter a valid Maximum Program Scan Time word (i.e., less
than or equal to 128*NUT) into word 13 of the ControlNet
Backup Configuration and Status file.

11

Handshake Requested Packet Interval (RPI) invalid

Make the handshake connection’s RPI in the I/O map table
at least one NUT, but less than 2 NUTs.

12

Crossload file number parameters invalid

Enter valid file numbers (0 - 999) into words 55 through 58
of the ControlNet Backup Configuration and Status file
Make sure the crossload range low word (word 57) value
is less than or equal to the crossload range high word
(word 58) value.

13

ControlNet NUT not established. Until the processor
is attached to the ControlNet channel, the NUT is
unknown.

Attach the processor to the ControlNet channel.

14

Invalid crossload channel configuration

Set the value in word 70 of the CBI file:
0 = Crossload over Channel 2 (ControlNet - default)
1 = Crossload over Channel 1A (DH+)
Additional causes for this fault:
- Channel 1A must be configured to DH+
- Channel 1A baud rate must be 230.4Kbaud
- Odd-numbered ControlNet PLC-5 DH+ address must be 1
- Even-numbered ControlNet PLC-5 DH+ address must be 2
Change these settings by adjusting Channel 1A DIP
switches:

15

Keeper not configured

Download correct network information using RSNetWorx

16

Signature mismatch

Download correct network information using RSNetWorx

17

Handshake connections not scheduled

Enter proper handshake connections using RSNetWorx

18

Invalid configuration parameter

Set the value in word 72 of the CBI file:
0 = No requalification with dual primary (default)
1 = Requalification with dual primary