Publication 1785-UM024B-EN-P - January 2003

Installing and Configuring Your ControlNet PLC-5 Backup System 3-23

Once you have selected the files you wish to crossload, click on the
Crossload User Files button to perform the operation. Note that you
can perform a crossload for individual files and for a range of files
simultaneously.

System Status

You can view system status from the Status tab of the ControlNet Hot
Backup screen.

The CBC Module LEDs section mirrors the display of the LEDs on the
1785-CHBM module which is currently online.

Diagnostic Counters

Diagnostic counters provide information on the number of times the
Maximum Program Scan has exceeded the Maximum Program Scan
Time configured for the system when in Synchronous mode. These
counters are incremented by 1 every time the actual program scan is
greater than the configured program scan. The Lost Partner counter
increments every time the system has detected a loss of
communication between the primary and secondary PLC processors.
You can press the Clear button to reset these values.

Qualification Error Reason

If the qualification of the system fails, the Qualification Error Reason
indicates the reason why the failure occurred. Refer to Chapter 5 for
information on corrective actions you can take.