Connect the 1769-ba battery – Rockwell Automation 1769-L32C_L35CR CompactLogix Controller Installation Instructions User Manual
Page 12

12 1769-L32C, 1769-L35CR CompactLogix Controller
Publication
1769-IN070C-EN-P - May 2008
Connect the 1769-BA Battery
The controller is shipped with the 1769-BA battery packed separately. To
connect the battery, follow this procedure.
1. Remove the battery door by sliding it forward.
2. Insert the battery connector into the black receptacle on the board.
The connector is keyed to be installed with the correct polarity.
ATTENTION
The 1769-BA battery is the only battery you can use with the 1769-L32C and
1769-L35CR controllers. The 1747-BA battery is not compatible with the
1769-L32C and 1769-L35CR controllers and may cause problems.
WARNING
When you connect or disconnect the battery, an electrical arc can occur. This
could cause an explosion in hazardous location installations. Be sure that
power is removed or the area is nonhazardous before proceeding.
For safety information on the handling of lithium batteries, including handling
and disposal of leaking batteries, see Guidelines for Handling Lithium
Batteries Technical Data, publication AG-5.4.
IMPORTANT
Do not remove the plastic insulation covering the battery. The insulation is
necessary to protect the battery contacts.