Use the AutoFlash Utility to Load Firmware
You can use the AutoFlash utility to load firmware through either a
ControlNet connection or a serial connection.
1. Make sure the appropriate network connection is made before
starting.
2. Use RSLogix 5000 programming software to attempt to download to
a controller project.
This automatically launches AutoFlash.
3. Select the catalog number of the controller and click Next.
4. Expand the network until you see the controller, noting that if the
required network is not shown, you must first configure a driver for
the network in RSLinx software.
5. Select the controller and click OK.
6. Select the revision level to which you want to update the controller
and click Next.
7. To start the update of the controller, click Finish and click Yes, noting
that after the controller is updated, the status box displays Update
complete.
8. Click OK.
9. Click Cancel and Yes to close AutoFlash software.