1769-L32C, 1769-L35CR CompactLogix Controller 21

Publication

1769-IN070C-EN-P - May 2008

6. Attach the modules to the panel by using the mounting screws.

7. Repeat steps 1…6 for any remaining modules.

DIN-rail Mounting

The controller can be mounted by using the following DIN rails:

• EN 50 022 - 35 x 7.5 mm (1.38 x 0.30 in.)
• EN 50 022 - 35 x 15 mm (1.38 x 0.59 in.)

Before mounting the controller on a DIN rail, close the DIN rail latches.
Press the DIN rail mounting area of the controller against the DIN rail. The
latches will momentarily open and lock into place.

This product is intended to be mounted to a well-grounded mounting surface,
such as a metal panel. Additional grounding connections from the controller’s
grounding tab or DIN rail (if used) are not required unless the mounting
surface cannot be grounded.
Refer to Industrial Automation Wiring and Grounding Guidelines,
Allen-Bradley publication 1770-4.1, for additional information.

IMPORTANT

If mounting more modules, mount only the last one of this group and put the
others aside. This reduces remounting time when you are drilling and
tapping the next group of modules.

ATTENTION

This product is grounded through the DIN rail to chassis ground. Use zinc
plated yellow-chromate steel DIN rail to assure proper grounding. The use of
other DIN rail materials (for example, aluminum and plastic) that can corrode,
oxidize, or are poor conductors, can result in improper or intermittent
grounding. Secure DIN rail to mounting surface approximately every 200 mm
(7.8 in.) and use end-anchors appropriately.