30 1769-L32C, 1769-L35CR CompactLogix Controller

Publication

1769-IN070C-EN-P - May 2008

Connect a Programming Terminal to the Network Via a 1786-CP Cable

You can use the CompactLogix controller’s network access port (NAP) to
connect a programming terminal to the ControlNet network. The figure
shows the 1786-CP cable connections.

.

WARNING

The NAP port is intended for temporary local-programming purposes only and
not intended for permanent connection. If you connect or disconnect the NAP
cable with power applied to this module or any device on the network, an
electrical arc can occur. This could cause an explosion in hazardous location
installations.
Be sure that power is removed or the area is nonhazardous before proceeding.

ATTENTION

Use the 1786-CP cable when you connect a programming terminal to the
network through the NAP.

Using another cable could result in possible network failures or product
damage.

Shield

GND REF

+24V DC

PTTx_H

PTTx_L

PTRx_L

PTRx_H

+24V DC

GND REF

8

7
6

5

4
3

2

1

1

2
3

4

5
6

7

8

Shield

GND REF

+24V DC

PTRx_H

PTRx_L

PTTx_L

PTTx_H

+24V DC

GND REF

3.05 m
(10 ft)

This cable is not a straightthrough cable.