Connect a Programming Terminal to the Controller Via RS-232 Connections

Use an RS-232 cable to connect your CompactLogix controller to your
programming terminal. You can use either of the following RS-232 cables:

• 1747-CP3
• 1756-CP3

The figure shows the RS-232 cable connections. The 1747-CP3 or 1756-CP3
cable must be shielded and tied to the connector housing.

WARNING

If you connect or disconnect the serial cable with power applied to this module
or the serial device on the other end of the cable, an electrical arc can occur.
This could cause an explosion in hazardous location installations.

Be sure that power is removed or the area is nonhazardous before proceeding.

Item

Description

1

9-pin, male D-shell straight cable end

2

9-pin, female D-shell right-angle cable end

Shield

GND REF

+24V DC

PTTx_H

PTTx_L

PTRx_L

PTRx_H

+24V DC

GND REF

8

7
6

5

4
3

2

1

1

2
3

4

5
6

7

8

Shield

GND REF

+24V DC

PTRx_H

PTRx_L

PTTx_L

PTTx_H

+24V DC

GND REF

3.05 m
(10 ft)

This cable is not a straightthrough cable.