1769-L32C, 1769-L35CR CompactLogix Controller 25

Publication

1769-IN070C-EN-P - May 2008

Default Serial Configuration

Channel 0 (serial) has the following default communication configuration.

Using the Channel 0 Default Communication Push Button

The channel 0 default communication pushbutton is on the front of the
controller in the lower right corner as shown in the figure.
Use the pushbutton to change from the user-defined communication
configuration to the Default Communications mode.

Channel 0 Serial Default Communication Configuration

Parameter

Default

Protocol

DF1 full-duplex

Baud Rate

19.2 Kbit/s

Parity

None

Station Address

0

Control Lines

No handshaking

Error Detection

BCC

Embedded Responses

Auto detect

Duplicate Packet (Message) Detect

Enabled

ACK Timeout

50 (x 20 ms)

NAK Receive Limit

3 retries

ENQ Transmit Limit

3 retries

Data Bits

8

Stop Bits

1