Default Serial Configuration
Channel 0 (serial) has the following default communication configuration.
Using the Channel 0 Default Communication Push Button
The channel 0 default communication pushbutton is on the front of the
controller in the lower right corner as shown in the figure.
Use the pushbutton to change from the user-defined communication
configuration to the Default Communications mode.
Channel 0 Serial Default Communication Configuration
Parameter
Default
Protocol
DF1 full-duplex
Baud Rate
19.2 Kbit/s
Parity
None
Station Address
0
Control Lines
No handshaking
Error Detection
BCC
Embedded Responses
Auto detect
Duplicate Packet (Message) Detect
Enabled
ACK Timeout
50 (x 20 ms)
NAK Receive Limit
3 retries
ENQ Transmit Limit
3 retries
Data Bits
8
Stop Bits
1