Verify Proper Controller Operation

To verify that your controller is operating properly, use the controller’s various
status indicators as shown in the tables.

REM - Remote Run

• The controller executes (scans) tasks.
• Enable outputs.
• Edit online.

REM - Remote Program

• Disable outputs.
• Create, modify, and delete tasks, programs or

routines.

• Download projects.
• Edit online.
• The controller does not execute (scan) tasks.

REM - Remote Test

• Execute tasks with outputs disabled.
• Edit online.

Controller Status Indicators

Indicator

Status

Description

RUN

Off

The controller is in Program or Test mode.

Steady green

The controller is in Run mode.

FORCE

Off

No tags contain I/O force values.
I/O forces are inactive (disabled).

Steady amber

I/O forces are active (enabled).
I/O force values may or may not exist.

Flashing amber

One or more input or output addresses have been
forced to an On or Off state, but the forces have not
been enabled.

BAT

Off

The battery supports memory.

Steady red

Either the battery is:

• not installed and should be installed.
• 95% discharged and should be replaced.