You can also use these components with the controller:

• 1784-CF64 or 1784-CF128 Industrial CompactFlash card to add

nonvolatile memory

• 1756-CP3 or 1747-CP3 serial cable to connect a device to the

RS-232 port

• Either of the following to connect to the ControlNet network:

• ControlNet taps for connections from controller channels A or B

to the ControlNet network

• 1786-CP cable for connections from a programming terminal to

the ControlNet network via the controller’s network access
port (NAP)

Consider the following when planning your CompactLogix system:

• The CompactLogix controller is always the leftmost module in the

system.

• The CompactLogix controller must be located within four modules of

the power supply.

• Some I/O modules can be located up to eight modules away from the

power supply; see the documentation for your 1769 I/O modules
for details.

• The 1769-L32C controller supports as many as 16 I/O modules in a

maximum of 3 I/O banks with 2 expansion cables.

• The 1769-L35CR controller supports as many as 30 I/O modules in a

maximum of 3 I/O banks with 2 expansion cables.

• Each I/O bank requires its own power supply.

• Only one controller can be used in a CompactLogix system.