Network channel status indicators – Rockwell Automation 1769-L32C_L35CR CompactLogix Controller Installation Instructions User Manual

Page 43

Advertising
background image

1769-L32C, 1769-L35CR CompactLogix Controller 43

Publication

1769-IN070C-EN-P - May 2008

Network Channel Status Indicators

Only channel B is labeled on the 1769-L35CR controller. The 1769-L32C
controller has only channel A but uses the second indicator in some status
indicator patterns as described in the table.

Network Channel Status Indicators

Indicator Status

Description

Both channel
indicators

Off

A channel is disabled. Program network for redundant
media, if necessary.

Steady green

Normal operation is occurring.

Flashing
green/off

Temporary network errors have occurred. Check media
for items such as broken cables, loose connectors, and
missing terminators. If condition persists, refer to the
ControlNet Planning and Installation Manual,
publication 1786-6.2.1.

The node is not configured to go onlineMake sure the
network keeper is present and working and the

selected address is less or equal to the UMAX

(1)

.

Flashing red/off

Media fault has occurred. Check media for items such
as broken cables, loose connectors, and missing
terminators. If condition persists, refer to the
ControlNet Planning and Installation Manual,
publication 1786-6.2.1.

No other nodes present on the network. Add other
nodes to the network.

Flashing
red/green

The network is configured incorrectly. Reconfigure the
ControlNet network so that UMAX > the card’s node
address.