Interpret the led indicators, Led indicator descriptions – Rockwell Automation 1785-ENET PLC-5 Ethernet Interface Module Installation Instructions User Manual

Page 43

Advertising
background image

PLC-5 Ethernet Interface Module 43

Publication 1785-IN019B-EN-P - January 2007

Interpret the LED Indicators

If your module is operating correctly, you see:

• Status LED indicator remains lit green
• Ethernet Transmit LEDs briefly light green when transmitting packets

If the LED indicators do not indicate the above normal operation, refer to the following
table.

LED Indicator Descriptions

TCP

tcpInSegs

Number of segments received

tcpOutSegs

Number of segments sent

tcpRetransSegs

Number of segments retransmitted

tcpInErrors

Number of segments discarded due to format errors

tcpOutRsts

Number of resets generated

tcpConnState

State of connection

tcpConnLocalAddress

Local IP address

tcpConnLocalPort

Local TCP port

tcpConnRemAddress

Remote IP address

tcpConnRemPort

Remote TCP port

Indicator

Color

Description

Probable Cause

Recommended Action

STAT

Solid red

Critical hardware fault.

Module requires internal
repair.

Contact your local
Allen-Bradley distributor.

Blinking red

Hardware or software fault (detected
and reported via a code).

Fault-code dependent.

Refer to module error codes.

Off

Module is functioning properly but it is
not attached to an active Ethernet
network.

Normal operation.

Attach the controller and
interface module to an
active Ethernet network.

Green

Ethernet channel 3A is functioning
properly and has detected that it is
connected to an active Ethernet network.

Normal operation.

No action required.

100M or
10M

Green

Lights (green) briefly when the Ethernet
port is transmitting a packet. It does not
indicate whether or not the Ethernet port
is receiving a packet.

Group

MIB

Description

Advertising