46 PLC-5 Ethernet Interface Module

Publication 1785-IN019B-EN-P - January 2007

Environmental Specifications

Attribute

Value

Operating Temperature

IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
0...60

o

C (32...140

o

F)

Storage Temperature

IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),
IEC 60068-2-2 (Test Bc, Unpackaged Nonoperating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock):
–40...85

o

C (–40...185

o

F)

Relative Humidity

IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
5...90% noncondensing

Vibration

IEC 60068-2-6 (Test Fc, Operating):
2 g @ 10...500 Hz

Shock, Operating

IEC 60068-2-27 (Test Ea, Unpackaged shock):
30 g

Shock, Nonoperating

IEC 60068-2-27 (Test Ea, Unpackaged shock):
50 g

Emissions

Group 1, Class A (with appropriate enclosure)

ESD Immunity

IEC 61000-4-2:
6 kV indirect contact discharges

Radiated RF Immunity

IEC 61000-4-3:
10V/M, with 1 kHz sine-wave 80% AM from 80...2000 MHz

10V/M with 200 Hz 50% Pulse 100% AM at 900 MHz

10V/M with 200 Hz 50% Pulse 100% AM at 1890 MHz

EFT/B Immunity

IEC 61000-4-4:
+2 kV at 5 kHz on shielded communications ports

+1 kV at 5 kHz on unshielded communications ports

Surge Transient Immunity

IEC 61000-4-5:
+2 kV line-earth (CM) on communications ports

Conducted RF Immunity

IEC 61000-4-6:
10V rms with 1kHz sine-wave 80% AM from 150 kHz...80 MHz

Enclosure Type Rating

None (open style)