Module error codes – Rockwell Automation 1785-ENET PLC-5 Ethernet Interface Module Installation Instructions User Manual

Page 44

Advertising
background image

44 PLC-5 Ethernet Interface Module

Publication 1785-IN019B-EN-P - January 2007

Monitor the series of blinks to determine the fault code. Count the first and last series of slow
blinks, and disregard the series of fast blinks between the slow series.

Module Error Codes

When the status LED blinks red, it signals that a hardware or software fault has been detected
and it reports the error via a code. This code is a two-digit fault code signaled by a flash
sequence. First, the LED begins the sequence with 10 rapid flashes. Then the LED signals the
first digit of the code by a number of slow flashes. Approximately two seconds after the LED
displays the first digit, the LED displays the second digit. This sequence repeats itself until the
module is either reset or replaced.

The following table lists controller fault codes relating to the interface module.

IMPORTANT

The interface module will flash the indicator lights as shown in the
Module Error Codes table. The controller may fault even though the
module does not.

Code

Description

Code

Description

01

General 68000 test failure

36

PLC-5 dual-port initialization failure

02

Bus error

37

PLC-5 not compatible with 1785-ENET

03

Address error

38

Dual-port diagnostic failure

04

Illegal instruction

41

Could not read FLASH id

05

Divide by zero

42

Could not erase FLASH bank

06

Reserved

43

Could not program FLASH bank

07

Reserved

51

Software initialization failure

08

Privileged instruction

52

ENET firmware hardware fault

09

Trace trap

53

ENET software failure

10

Line 1010 instruction

54

Network system failure

11

Line 1111 instruction

55

Dual-port system failure

12

Hardware breakpoint

56

Dual-port internal inconsistency

13

Reserved

57

ISR system failure

14

Uninitialized interrupt

58

ISR internal inconsistency

15

Format error

61

Lump system call failed

16

Reserved

62

Lump internal inconsistency

24

Spurious interrupt

63

PCCC system call failed

25

TRAP in instruction

64

PCCC internal inconsistency

26

Unassigned user

65

Dual-port system call failed

27

Unassigned reserved

66

Dual-port internal inconsistency

31

OS area checksum not valid

71

AC power fail

32

Static RAM self-test failed

72

Reset asserted

33

Jump table wrong

73

Fault asserted

34

Ethernet chip test failed

74

Watchdog timeout

35

FLASH BOOT area checksum incorrect

75

Unknown NMI

Advertising