Overview of the
1779ĆKP5 Module
Chapter 2
2Ć4
Connecting Data Highway Plus to Data Highway II
Figure 2.4 shows an example of using a 1779-KP5 to connect a Data
Highway Plus link to a Data Highway II link.
Figure 2.4
Connecting Data Highway Plus to Data Highway II
1779ĆKP5
Data Highway II
1784ĆT50
PLCĆ5
PLCĆ5
Data Highway
Plus
16482
Important: When you connect a Data Highway Plus link to a Data
Highway II link, you must observe the following limitations:
A computer connected to a Data Highway Plus (through a 1785-KE or
1770-KF2 module) cannot access nodes on a Data Highway II through
a 1779-KP5 module.
Nodes on Data Highway II cannot access a computer connected to Data
Highway Plus.
A 1784-T50 on a Data Highway Plus link cannot program devices on
another Data Highway Plus link through the 1779-KP5.
A computer on a Data Highway II, however, can access a PLC on Data
Highway Plus through a 1779-KP5.