Installing the 1779ĆKP5 Module
Chapter 3
3Ć8
For example, to set a Data Highway Plus link address of 5 and a Data
Highway II link address of 6, you would set the switches as follows:
OPEN
1
2
3
4
5
6
7
8
16499
1 + 4
5
2 + 4
6
Switch Assembly SĆ4: Enable/Disable Route Update
You use Switch Assembly S-4 to enable or disable the route update
message on your network.
OPEN
1
2
3
4
16500
Reserved
Route Update
Enable/Disable
When you press a
switch
towards the word OPEN,
you turn the switch ON.
If You Are Using:
Then:
A 1779ĆKP5 as an Interface between a Data
Highway Plus Link and Data Highway II
Disable Route Updates
(Both Switches OFF Ċ Closed)
A 1779ĆKP5 in a Bridge Configuration
Enable Route Updates
(Both Switches ON Ċ Open)