Addressing from Data Highway Plus

Chapter 5

5Ć7

Figure 5.2

Data Highway Plus to Remote Data Highway II Configuration

1779ĆKP5

1779ĆKP5

Data Highway Plus

Data Highway II

(Do not attach nodes

when used in bridge

configuration.)

Data Highway II

1779ĆKP5

1784ĆT50

PLCĆ5

PLCĆ5

Data

Highway

Plus

1779ĆKFL

16494

The LINK value is the link value of the remote Data Highway II link.
You set this number with switches on the 1779-KP5 (refer to Chapter 3).

The NODE value of a Data Highway II node is the node address you set
on the module using the thumbwheels on the front panel.

The default USER value for all Data Highway II devices is 01. For a
1779-KFL module, the devices will have USER values of 01 and 02.

For example, a node on Data Highway II Link 03, Address 15, connected
to a 1779-KFL User 2, would have the address:

USER

02

NODE

15

LINK

03

Important: The address of the initiating Data Highway Plus node must
be between 02 and 20 (octal) so that the reply message can be returned. A
computer on Data Highway Plus cannot address a node on a remote link,
such as Data Highway II or another Data Highway Plus link.