Rockwell Automation 1779-KP5_KP5R ORD.1779-5.3 User Manual

Page 59

Advertising
background image

1779ĆKP5 Troubleshooting Tools

Chapter 6

6Ć4

When the module is passing the token or sending messages on a small
network, the RECEIVE LED appears to remain lit and the TRANSMIT
LED flickers.

Using the LEDs to Troubleshoot the Module

When you suspect that the 1779-KP5 is not functioning properly, use the
following troubleshooting flowchart (Figure 6.3).

Figure 6.3

Troubleshooting Flowchart

AC

Step 1

OFF

POWER

ON

Problem
Suspected

HOST
FAULT

MAC
FAULT

DUP
ADDR

IN-RING/
SEEKING

MEM

ON

DC

POWER

ON

Step 2

Press EXIT REQUEST switch.
When the exit is confirmed,
switch to RESET momentarily

Step 3

Step 4

Step 5

Step 6

ON

OFF

OFF

OFF

Green

OFF

ON

ON

ON

Yellow

Check:

AC POWER Switch
Fuse

Check the ribbon cable
connectors between the boards.

Replace host board.

Replace MAC board.

Press EXIT REQUEST.
Set unique link address.

Check cabling on Data

Communication on Data
Highway II link OK. Check
cabling to the host device.

Set the AC power switch to OFF,
wait 20 seconds, then set the AC

AC Power Source
Interlock Switch
Power-Supply Board

power switch to ON. If the indi–
cator is still OFF, try replacing

Highway II link.

each of the three boards until
you find the faulted one.

and then to RUN.

13986

Advertising