Setting the node address – Rockwell Automation 1779-KP5_KP5R ORD.1779-5.3 User Manual
Page 17

Installing the 1779ĆKP5 Module
Chapter 3
3Ć4
Set the node address for your module using the three thumbwheels on the
front panel of your module (Figure 3.3).
Figure 3.3
Address Thumbwheels on the Front Panel of the Module
MSD
LINK
ADDRESS
EXIT
COMPLETE
EXIT
REQUEST
G
IN RING
Y
SEEKING MEM
DUP ADDR
MAC FAULT
MAC TEST
NODE PASS
HOST FAULT
NODE TEST
TEST
RUN
RESET
ACTIVITY
SAT
TRANSMIT
RECEIVE
READY
ERROR
16009
Set these thumbwheels to designate the node address of the 1779-KP5 for
both Data Highway II and Data Highway Plus. The top thumbwheel
represents the most significant digit (MSD). Set this digit to zero, since
the highest address available to a Data Highway Plus node is 077 (octal).
The bottom two thumbwheels do not go past the digit seven because the
address must be an octal number. Each node on your network must have
a unique address.
Important: The 1770-T3 industrial terminal (for the PLC-2) cannot
communicate with Addresses 000 through 007 and Addresses 100 through
107 (octal). If you have PLC-2s on your Data Highway II network, you
may not want to use these node addresses.
Setting the Node Address