1779ĆKP5 Troubleshooting Tools

Chapter 6

6Ć6

Diagnostic Status Bytes for Data Highway Plus

Data Highway Plus diagnostic status bytes can be read from an intelligent
device (computer) connected to your Data Highway Plus network. The
following table contains a list of the 1779-KP5’s diagnostic status bytes
for Data Highway Plus:

Byte

Number

Description

1

00 = Not Used

2

Interface/Processor Type

EE = See Expansion Bytes (Bytes 3 and 4)

3

Interface Type Expansion Byte

1A = 1779ĆKP5

4

Processor Type Expansion

Byte

17 = Data Highway Plus Information

5, 6

00 = Not Used

7, 8

Address of Active Node Table

Byte 7 = Low Byte

Byte 8 = High Byte

9, 10

Diagnostic Counter Address

Byte 9 = Low Byte

Byte 10 = High Byte

11

Series and Revision

Bits 0Ć4

0 = Revision A

1 = Revision B

Etc.

Bits 5Ć7

0 = Series A

1 = Series B

Etc.

12

Option Switches

Bits 0Ć3: SWĆ5 Data Highway Plus Baud Rate

02 = 230 Kb

04 = 115 Kb

06 = 57.6 Kb

Bits 4Ć7: SWĆ4 Route Updates

00 = Route Updates Disabled

03 = Route Updates Enabled

Advertising