Application trusts (pi server) – Rockwell Automation FactoryTalk Historian ME 2.2 Quick Start Guide User Manual

Page 35

Advertising
background image

T

RANSFERRING

D

ATA

31

• •

An informational message that states that the connection to SE
was established displays at the top of the page if the
connection is successful. In addition, a green checkmark
displays next to the [Test Connection] button. This indicates
that the module can establish a connection to your FactoryTalk
Historian SE server. If this checkmark and message do not
appear, check your work and try again.

4.

Click [Save].

You have completed the trust configuration process.

Application Trusts (PI Server)

To successfully transfer data between FactoryTalk Historian ME
and the PI server, you must create two application trusts on the PI
server: webs and datatransfer. To do so, perform the following
steps:

1.

Launch the OSIsoft SMT application from where you installed
it. Navigate to System Management Tools.

2.

After SMT launches, go to the Collectives and Servers pane
and click the checkbox next to the PI server you want to create
a trust for.

3.

Under the System Management pane, click [+] next to Security
and then select Mappings and Trusts.

4.

In the Trusts tab in the main window, select the drop-down
menu on the New option. The Wizard option is checked by
default.

The Add Trust Wizard window is launched. The Trust Wizard
creates a trust on the PI server that is currently selected.

Advertising