Configure the synchlink module – Rockwell Automation 1756-SYNCH ControlLogix SynchLink Module User Manual User Manual
Page 108
 
Publication 1756-UM521C-EN-P - July 2004
C-14 Configuring the Daisy Chain Configuration
Configure the SynchLink Module
1. Use the new module creation wizard as shown below.
E. Electronic Keying
method is Compatible 
Module.
G. Click here after
completing the 
information on this page.
F. Minor Revision = 1.
A. Module name is
Time_Slave_End_Node.
B. Receive Port Comm Format is
2 Direct Words, 18 Buffered to 
match the upsteam device’s 
Transmit Port Comm Format.
C. Transmit Port Comm Format is
No Transmit Data.
D. Module slot number
is 3 as shown in the 
graphic on page C-1.
Requested Packet Interval = 20mS
Click here to continue configuration.
Click here to finish configuration.
Time slave modules must be 
configured as Time Masters for 
their respective chassis. With 
this setting, the Time Slave 
module passes the CST value 
(received from the Time Master 
chassis) to the local chassis 
backplane and all the devices in