Rockwell Automation 1756-SYNCH ControlLogix SynchLink Module User Manual User Manual
Page 87
 
Publication 1756-UM521C-EN-P - July 2004
Configuring the Star Configuration B-11
Create Axis Data Tags
You must create axis data tags for the controller in this chassis to consume. 
The axis data is originally produced in the Time Master chassis and broadcast 
to SynchLink modules in other chassis over the fiber optic cable. SynchLink 
modules in each Time Slave chassis then consume the data from the cable and 
produce it in the local chassis. The owner controller in their local chassis 
consumes the data from the local SynchLink module.
Follow these steps to create axis data tags in the consuming chassis:
1. Create a New Tag for Axis 0.
A. Select Controller Tags.
B. Right-click to display 
the menu.
C. Select New Tag.
A. Name the new tag. This axis
tag must be assigned to a 
valid motion group.
B. Change the Tag Type
to Consumed.
C. Use the pull-down menu
to change the Producer to 
the SynchLink module in
the local chassis.
D. Type in the Remote Tag
Name. This name must 
either be Axis0 or Axis1.
IMPORTANT: If you use any 
Remote Tag Name other 
than Axis0 or Axis1, the 
remote axis data will NOT 
be consumed.
E. Change the Data Type to Axis or
Consumed Axis, depending on your 
version of RSLogix 5000.
F. Click on OK to create the new tag.