Rockwell Automation 1756-SYNCH ControlLogix SynchLink Module User Manual User Manual
Page 35
 
Publication 1756-UM521C-EN-P - July 2004
SynchLink Module Features 3-7
Multiple Port Communications Formats in Single Module
You must set a communications format for receiving data (Receive Port 
Communications Format) and transmitting data (Transmit Port 
Communications Format) in each SynchLink module. The following 
requirements apply to communication format choices:
• If a SynchLink module does not receive data (e.g. a SynchLink
Time Master in a star or daisy chain configuration), you must 
choose the No Receive Data Receive Port communication format.
• If a SynchLink module does not transmit data (e.g. an end
node), you must choose the No Transmit Data Transmit Port 
communications format.
• The receive communication format for any SynchLink module
that receives data must match the transmit communications 
format of the upstream node in the system. For example, if the 
Time Master SynchLink module uses a 2 Axis Transmit Port 
communication format, the SynchLink module physically 
connected to the Time Master must use a 2 Axis Receive Port 
communications format.
• If a SynchLink module is used to provide CST signals to remote
I/O chassis, you can choose any communication format except 
No Receive Data, Listen Only or No Transmit Data. CST signals 
are used in the remote chassis to synchronize I/O timestamps. In 
this case, the data words transmitted over SynchLink are 
not used. 
IMPORTANT
The receive and transmit on the same module do not 
have to match.
Also, once the module is created, you cannot change 
the communications format. You must delete and 
recreate the module.