Rockwell Automation 1756-SYNCH ControlLogix SynchLink Module User Manual User Manual

Page 38

Advertising
background image

Publication 1756-UM521C-EN-P - July 2004

3-10 SynchLink Module Features

The Communications Format feature is configured on the following screen.

Table 3.5 SynchLink Module Transmit Communications Formats

Transmit Port Communications Format

Transfer Rate (across the fiber optic
cable) for Each Data Type:

1 Axis, 3 Direct Words, 14 Buffered

Axis Data - Updated every 500

μS

Direct Data - Updated every 50

μS

Buffered Data - Updated every 500

μS

2 Axis

Axis Data - Updated every 250

μS

2 Axis, 3 Direct Words

Axis Data - Updated every 500

μS

Direct Data - Updated every 50

μS

2 Direct Words, 18 Buffered

Direct Data - Updated every 50

μS

Buffered Data - Updated every 250

μS

4 Direct Words, 18 Buffered

Direct Data - Updated every 50

μS

Buffered Data - Updated every 500

μS

4 Direct Words, 8 Buffered

Direct Data - Updated every 50

μS

Buffered Data - Updated every 250

μS

Listen Only, No Transmit Data

No data updated in this format

No Transmit Data

No data updated in this format

Communications Formats