Time Synchronization in the ControlLogix System 2-5
How Do the CST Clock and 
SynchLink Node Clock 
Work Together?
As stated earlier, the ControlLogix Coordinated System Time clock 
(CST) is a 64-bit clock on the ControlLogix backplane. It is used as the 
main time reference for all modules plugged into a ControlLogix 
chassis. The SynchLink node clock is used to establish the time 
reference on the SynchLink fiber. 
Figure 2.4 illustrates how the SynchLink node clock and the CST time 
reference are coordinated in a system. In this example, the SynchLink modules 
in chassis A & B synchronize the CST clock in chassis B with the CST 
reference in chassis A.
Chassis A is the Time Master for the system. When the SynchLink 
module strobes the beacon signal onto the fiber optic link, it also 
transmits the CST time reference value that tells the downstream node 
what time it is as the beacon occurs. The downstream chassis receives 
the CST time reference and synchronizes its time with the CST 
reference value on the beacon signal.
Figure 2.4
Configuring Time 
Mastership Functionality
You must configure each 1756-SYNCH module’s role in Coordinated 
System Time (CST) Mastership. For any SynchLink system, there can 
only be one SynchLink CST Time Master for the system; the Time 
Master can be a 1756-SYNCH module or a ControlLogix controller. All 
other devices connected to the SynchLink must be configured as Time 
Slaves. However, the 1756-SYNCH modules that are Time Slaves are 
Chassis CST Masters that receive the SynchLink time from the fiber 
optic cable and relay it to all devices in their local chassis.
For example, the 1756-SYNCH modules in Figure 2.4 can be configured as 
follows:
• 1756-SYNCH in Chassis A - MUST be SynchLink CST Master;
CAN also be Chassis CST Master
• 1756-SYNCH in Chassis B - MUST be Chassis CST Master;
CANNOT be SynchLink CST Master
For a full explanation on how to configure CST and SynchLink Mastership, 
see page 3-18.
Chassis A
Chassis B
Coordinated System Time
Coordinated System Time
64-bit clock
1756-SYNCH
1756-SYNCH
SynchLink Node Clock
Clock
SynchLink beacon over the fiber optic link