Configure the synchlink module – Rockwell Automation 1756-SYNCH ControlLogix SynchLink Module User Manual User Manual
Page 81

Publication 1756-UM521C-EN-P - July 2004
Configuring the Star Configuration B-5
Configure the SynchLink Module
1. Use the new module creation wizard as shown below.
E. Electronic Keying
method is Compatible
Module.
G. Click here after
completing the
information on this page.
F. Minor Revision = 1.
A. Module name is
Time_Master.
B. Receive Port Comm Format is
No Receive Data because the
module is the master of a Star
and does not receive data.
C. Transmit Port Comm Format is
2 Axis.
D. Module slot number
is 3 as shown in the
graphic on page B-1.
Click here to move to the next page
Requested Packet Interval =
Click here to move to the next page
Use the pull-down menu, to choose
which axis data tags to transmit over
each axis. This menu lists the Axis
tags currently defined in the project.
Use this button to define a new
Axis tag.
IMPORTANT: All produced tags
must be checked as produced tags in
the Tag Editor. For more information