Configure the SynchLink Module
1. Use the new module creation wizard as shown below.
E. Electronic Keying
method is Compatible 
Module.
G. Click here after
completing the 
information on this page.
F. Minor Revision = 1.
A. Module name is
Time_Master.
B. Receive Port Comm Format is
No Receive Data because the 
module is the master of a Star 
and does not receive data.
C. Transmit Port Comm Format is
2 Axis.
D. Module slot number
is 3 as shown in the 
graphic on page B-1.
Click here to move to the next page
Requested Packet Interval =
Click here to move to the next page
Use the pull-down menu, to choose 
which axis data tags to transmit over 
each axis. This menu lists the Axis 
tags currently defined in the project.
Use this button to define a new
Axis tag. 
IMPORTANT: All produced tags 
must be checked as produced tags in 
the Tag Editor. For more information