SynchLink Module Features 3-9
The SynchLink module updates its receive and transmit buffers once 
every 500μS. Because direct data can be passed through from node to 
node once every 50μS, up to 10 nodes can be updated with direct 
data in a single 500μS SynchLink scan. Pass-through functionality only 
applies to direct data in a daisy chain configuration, though; axis data 
and buffered data cannot be passed through. Instead, these data types 
require the intervention of the local controller to move data along. For 
this reason, it is not recommended that a daisy chain configuration 
be used when distributing axis data among multiple axis in a 
distributed control system.
For more information on the available Receive Port and Transmit Port 
communication formats, see Table 3.4.
Table 3.4 SynchLink Module Receive Communications Formats
Receive Port Communications Format
Transfer Rate (across the fiber optic 
cable) for Each Data Type:
1 Axis, 3 Direct Words, 14 Buffered
Axis Data - Updated every 500
μS
Direct Data - Updated every 50
μS
Buffered Data - Updated every 500
μS
2 Axis
Axis Data - Updated every 250
μS
2 Axis, 3 Direct Words
Axis Data - Updated every 500
μS
Direct Data - Updated every 50
μS
2 Direct Words, 18 Buffered
Direct Data - Updated every 50
μS
Buffered Data - Updated every 250
μS
4 Direct Words, 18 Buffered
Direct Data - Updated every 50
μS
Buffered Data - Updated every 500
μS
4 Direct Words, 8 Buffered
Direct Data - Updated every 50
μS
Buffered Data - Updated every 250
μS
No Receive Data
No data updated in this format