Incoming/outgoing wire installation, Install conduit, Install cable – Rockwell Automation 1748 DataSite Configured Panel Installation Instructions User Manual
Page 20: Install conduit install cable
 
Publication 1748-IN001B-EN-P - May 2009
20 Install and Wire the Panel
Incoming/Outgoing Wire 
Installation
Allowable incoming and outgoing voltages can range from 0V DC to 24V DC.
For details about field wiring apparatus, refer to the control drawing in the 
DataSite Hardware User Manual, publication 
Install Conduit
When installing conduit, make sure it is installed according to all applicable 
codes and standards. This is to ensure that water and moisture cannot enter or 
accumulate in the DataSite controller enclosure.
Conduits must be installed so they are compatible with the UL rating of the 
DataSite controller. It is recommended that the conduit be positioned to 
minimize cable bending and maintain relative vertical alignment to incoming 
connections.
Install Cable
Install cable when the ambient temperature is above freezing (0 °C or 32 °F), 
unless it is suitable for installation at temperatures below freezing. This will 
help prevent cable insulation from cracking or splitting.
DataSite controllers are rated for use with 75 °C (167 °F) cable. Cable must be 
sized using 75 °C (167 °F) column in NEC Table 310–16 (NEC 2005 Edition). 
IMPORTANT
Any conduit or cable entering or leaving the DataSite 
configured panel which is not deemed non-incendive must be 
held in conduit to maintain the UL Class I Division 2 Listing of 
that control panel.
ATTENTION
When installing the DataSite configured panel within a Class I 
Division 2, hazardous location, special installation of conduit 
and cable must be considered. Refer to NEC 2005 article 501 for 
details on proper installation of the conduit, cable, and box 
fittings.
TIP
To verify field wiring connection points, refer to the wiring 
diagrams in the DataSite Hardware User Manual, publication 
.